What are the standard recommendations for industrial flowmeter control cabinet layout design?

Comprehensive guide on industrial flowmeter control cabinet layout design standards

Industrial flowmeter control cabinet layout design directly affects system reliability and maintenance convenience. Layout recommendations for LGF electromagnetic flowmeters, HZ-KSLF radar flowmeters and related equipment include:

  • Functional zoning: Arrange by high-voltage, low-voltage, and communication zones, with high-voltage area for breakers and contactors, low-voltage area for RTU terminals EC32/EC60
  • Heat dissipation design: Reserve adequate ventilation space, avoid placing sensitive equipment above heat-generating components, add ventilation fans when necessary
  • Maintenance space: Equipment spacing ≥100mm, reserve 600mm maintenance channel in front of operating panels
  • Organized wiring: Use cable trays for classified wiring with clear labeling for easy troubleshooting
  • Protection rating: Outdoor cabinet protection rating ≥IP54, install anti-condensation heaters inside

For solar power supply systems, separate battery compartments with charge/discharge controllers are required. 4G communication modules should be installed in positions with minimal electromagnetic interference, with antenna outlets properly sealed and waterproofed to ensure long-term stable operation of the entire flow monitoring system.