Can the LGF-PA66 Be Installed on Vertical Pipes?

Yes. The LGF-PA66 supports horizontal, vertical and inclined mounting, but three rules must hold:Flo

Yes. The LGF-PA66 supports horizontal, vertical and inclined mounting, but three rules must hold:

  • Flooded first: the measuring tube must always run full. On vertical runs the flow should go bottom-to-top, so the pipe stays flooded at low flow or when a pump reverses; top-to-bottom vertical mounting is not recommended - the tube may not stay full and accuracy suffers.
  • Keep the electrode axis horizontal: on horizontal pipes, orient the two measuring electrodes on the horizontal centerline (never straight up/down), so gas bubbles cannot collect on the upper electrode and sediment cannot blanket the lower one.
  • Meet straight-run requirements: >= 5D upstream and >= 3D downstream (D = pipe diameter); add more upstream length or a flow conditioner when elbows, valves or pumps sit close by.

High points in a pipeline trap air - do not install the LGF-PA66 at the system's highest point; if unavoidable, fit an automatic air vent there. Low-lying valve pits are fine: the LGF-PA66 rating is IP68, supporting long-term immersed conditions.

The transmitter head rotates to multiple angles for easy reading on site; a split-type setup can move the transmitter outside the pit for convenient maintenance, linked to the sensor by dedicated shielded cable.

For more details, please visit our product pages or contact our technical team.

Installation & Maintenance