Should an electromagnetic flow meter be installed on the pump suction or discharge side? LGF-PA66 siting in pump stations

Install it on the discharge side whenever possible. On the suction side the meter sits under vacuum,

Install it on the discharge side whenever possible. On the suction side the meter sits under vacuum, where cavitation and degassing cause erratic readings, the flow profile is disturbed by elbows and reducers, and sustained vacuum stresses the flange-to-body seal. The LGF-PA66 has an all-insulated composite body with no liner to debond, but the positive-pressure siting rule still applies.

Siting checklist for pump stations:

  • Straight run ≥5D upstream and ≥2D downstream; extend the upstream run if a reducer sits close;
  • Avoid the highest point of the line (air pockets) and the lowest point (sediment); prefer a mid horizontal run or a vertical section with upward flow;
  • Flooded valve pits require the IP68-rated version; the PA66 body weighs about half of a comparable stainless-steel meter, which matters when lowering it into a confined pit;
  • With frequent pump cycling the PA66 body withstands water-hammer shocks well, and an EC32 RTU can alarm on flow transients to watch pump health.

If suction-side mounting is unavoidable, confirm the pump runs flooded-suction and keep the meter as close to the pump inlet flange as possible to shorten the vacuum section. Check pipe supports before installation — vibration from the pump outlet travels into the meter body and affects long-term sealing.

For more information, please visit our product pages or contact our technical team.