How do I troubleshoot jumps and drift in radar flow meter data? What quality-control measures exist?

Most anomalies in radar flow meter data trace back to an interference source or a parameter problem.

Most anomalies in radar flow meter data trace back to an interference source or a parameter problem. Work through this checklist on the HZ-KSLF and about 90% of jump/drift issues resolve on site.

Classify the anomaly first: level jumps usually mean the radar beam is hitting floating debris, weeds or surface foam; velocity jumps come from wind waves, heavy rain striking the surface, or strong EMI; slow drift typically indicates a loosened mounting bracket shifting beam aim, or siltation changing the actual wetted geometry.

Step-by-step checks:

  • Inspect the bracket and flange for looseness; verify beam verticality with an inclinometer — deviation should stay under 1°;
  • Clear floating debris, cobwebs and bird nests from the beam footprint; keep the antenna face clean;
  • Look for newly installed high-power VFDs or motors nearby — they can couple into the EC32 RTU through power lines; add a mains filter and check earthing if needed;
  • Verify level against a manual staff gauge; recalibrate the zero point if the difference exceeds 2 cm;
  • If velocity reads consistently high or low while level is normal, run a current-meter comparison and re-rate the velocity coefficient.

Quality control: the HZ-KSLF reports a built-in signal quality metric (SNR). On the platform side, enable three-tier QC — single-point range checks (flag physically impossible values), rate-of-change limits (flag suspicious jumps between samples), and level-velocity consistency checks. Combined with raw SNR uploaded via EC32, the platform can distinguish a genuine flood surge from device faults and suppress false alarms.

Set up monthly inspections: bracket tightness, antenna cleanliness, one staff-gauge cross-check — plus a velocity comparison before each flood season.

如需了解更多,请访问我们的产品页面或联系技术团队。

Installation & Maintenance