When the water level verified by camera disagrees with the radar reading, which one should I trust?
The camera and the radar inside a visual-fusion radar level meter are two independent measurement ch
The camera and the radar inside a visual-fusion radar level meter are two independent measurement chains, so occasional disagreement is normal. The ruling principle is clear: the radar value is the metrological reference, while the visual channel serves as condition verification — the radar chain outputs continuous ranging at ±1mm class, whereas camera readings depend on manual interpretation of a staff gauge, limited by viewing angle and resolution.
Three typical causes of discrepancy:
- Sampling time difference: an image is an instantaneous frame, while the radar level is averaged over a sampling window. With surface waves the two can legitimately differ by several centimetres — not a fault.
- Parallax: the staff gauge seen by the camera is not at the same spot as the radar beam's vertical measurement point. During installation, align and calibrate the visual reticle to the radar measurement point to remove systematic offset.
- Lens condition: raindrops, dust or condensation blur the image and mislead the reader; the radar channel does not depend on the lens and stays accurate. This is precisely the fault-tolerance value of the fusion design.
If the deviation persists beyond 5cm, check for newly added strong reflectors near the radar measurement point (metal brackets, cable trays) and whether wind or impact has shifted the mounting verticality. The echo spectrum can be read remotely via the EC60 RTU for diagnosis — most issues are located without a site visit, and installation parameters can be corrected remotely from the platform.